  <article-meta>
   <article-id pub-id-type="publisher-id">106326</article-id>
   <article-id pub-id-type="doi">10.61260/1998-8990-2025-3-133-142</article-id>
   <article-categories>
    <subj-group subj-group-type="toc-heading" xml:lang="ru">
     <subject>Пожарная безопасность</subject>
    </subj-group>
    <subj-group subj-group-type="toc-heading" xml:lang="en">
     <subject>Fire safety</subject>
    </subj-group>
    <subj-group>
     <subject>Пожарная безопасность</subject>
    </subj-group>
   </article-categories>
   <title-group>
    <article-title xml:lang="en">INFLUENCE OF THE HIGHT OF THE ROOM ON THE DISTRIBUTION OF SMOKE DURING A FIRE: STUDY BY NUMERICAL MODELING</article-title>
    <trans-title-group xml:lang="ru">
     <trans-title>ВЛИЯНИЕ ВЫСОТЫ ПОМЕЩЕНИЯ НА РАСПРОСТРАНЕНИЕ ДЫМА ПРИ ПОЖАРЕ: ИССЛЕДОВАНИЕ МЕТОДОМ ЧИСЛЕННОГО МОДЕЛИРОВАНИЯ</trans-title>
    </trans-title-group>
   </title-group>
   <contrib-group content-type="authors">
    <contrib contrib-type="author">
     <contrib-id contrib-id-type="orcid">https://orcid.org/0000-0002-5407-8394</contrib-id>
     <name-alternatives>
      <name xml:lang="ru">
       <surname>Османов</surname>
       <given-names>Шамиль Абубакарович</given-names>
      </name>
      <name xml:lang="en">
       <surname>Osmanov</surname>
       <given-names>Shamil A.</given-names>
      </name>
     </name-alternatives>
     <email>sh.osmanov@igps.ru</email>
     <xref ref-type="aff" rid="aff-1"/>
    </contrib>
    <contrib contrib-type="author">
     <contrib-id contrib-id-type="orcid">https://orcid.org/0000-0003-4053-7462</contrib-id>
     <name-alternatives>
      <name xml:lang="ru">
       <surname>Клюй</surname>
       <given-names>Валерий Владимирович</given-names>
      </name>
      <name xml:lang="en">
       <surname>Klyuj</surname>
       <given-names>Valery V.</given-names>
      </name>
     </name-alternatives>
     <email>val-1964@yandex.ru</email>
     <bio xml:lang="ru">
      <p>кандидат технических наук;</p>
     </bio>
     <bio xml:lang="en">
      <p>candidate of technical sciences;</p>
     </bio>
     <xref ref-type="aff" rid="aff-2"/>
    </contrib>
    <contrib contrib-type="author">
     <name-alternatives>
      <name xml:lang="ru">
       <surname>Козлова</surname>
       <given-names>Ирина Викторовна</given-names>
      </name>
      <name xml:lang="en">
       <surname>Kozlova</surname>
       <given-names>Irina V.</given-names>
      </name>
     </name-alternatives>
     <email>lisenoklll@mail.ru</email>
     <bio xml:lang="ru">
      <p>кандидат технических наук;</p>
     </bio>
     <bio xml:lang="en">
      <p>candidate of technical sciences;</p>
     </bio>
     <xref ref-type="aff" rid="aff-3"/>
    </contrib>
   </contrib-group>
   <aff-alternatives id="aff-1">
    <aff>
     <institution xml:lang="ru">Санкт-Петербургский университет ГПС МЧС России</institution>
     <city>Санкт-Петербург</city>
     <country>Россия</country>
    </aff>
    <aff>
     <institution xml:lang="en">Saint-Petersburg university of State fire service of EMERCOM of Russia</institution>
     <city>Saint-Petersburg</city>
     <country>Russian Federation</country>
    </aff>
   </aff-alternatives>
   <aff-alternatives id="aff-2">
    <aff>
     <institution xml:lang="ru">Санкт-Петербургский университет ГПС МЧС России</institution>
     <city>Санкт-Петербург</city>
     <country>Россия</country>
    </aff>
    <aff>
     <institution xml:lang="en">Saint-Petersburg university of State fire service of EMERCOM of Russia</institution>
     <city>Saint-Petersburg</city>
     <country>Russian Federation</country>
    </aff>
   </aff-alternatives>
   <aff-alternatives id="aff-3">
    <aff>
     <institution xml:lang="ru">Академия Государственной противопожарной службы МЧС России</institution>
     <city>Москва</city>
     <country>Россия</country>
    </aff>
    <aff>
     <institution xml:lang="en">Academy of State fire service of EMERCOM of Russia</institution>
     <city>Moscow</city>
     <country>Russian Federation</country>
    </aff>
   </aff-alternatives>
   <pub-date publication-format="print" date-type="pub" iso-8601-date="2025-10-21T00:00:00+03:00">
    <day>21</day>
    <month>10</month>
    <year>2025</year>
   </pub-date>
   <pub-date publication-format="electronic" date-type="pub" iso-8601-date="2025-10-21T00:00:00+03:00">
    <day>21</day>
    <month>10</month>
    <year>2025</year>
   </pub-date>
   <volume>2025</volume>
   <issue>3</issue>
   <fpage>133</fpage>
   <lpage>142</lpage>
   <history>
    <date date-type="received" iso-8601-date="2025-08-26T00:00:00+03:00">
     <day>26</day>
     <month>08</month>
     <year>2025</year>
    </date>
    <date date-type="accepted" iso-8601-date="2025-09-12T00:00:00+03:00">
     <day>12</day>
     <month>09</month>
     <year>2025</year>
    </date>
   </history>
   <self-uri xlink:href="https://journals.igps.ru/en/nauka/article/106326/view">https://journals.igps.ru/en/nauka/article/106326/view</self-uri>
   <abstract xml:lang="ru">
    <p>Для обеспечения безопасности граждан и объектов защиты в высотных зданиях проектируются и устанавливаются системы пожарной сигнализации. Одним из ключевых факторов при ее проектировании является характер распространения дыма&#13;
при пожаре, который, в свою очередь, сильно зависит от высоты потолков.&#13;
Предметом исследования выступает процесс распространения дыма при пожаре в помещениях различной высоты.&#13;
Методологическая база исследования включает численное моделирование данного процесса, которое было осуществлено в программном продукте Fire Dynamic Simulation с дальнейшей визуализацией данных в Smokeview.&#13;
Полученные данные свидетельствуют о том, что при высоте потолков 4 и 8 м вертикальный уровень задымления происходит быстрее горизонтального, в связи с чем на этих высотах предпочтительнее установка дымовых линейных извещателей традиционным способом (горизонтально). Начиная с высоты потолков в 12 м более выгодным является расположение дымовых линейных извещателей вертикально. Выявленные особенности могут быть полезны как на этапах проектирования, так и монтажа систем пожарной сигнализации. В рамках направлений дальнейших исследований целесообразно исследовать процесс распространения дыма в помещениях различной высоты и геометрии более детально и на основе полученных данных осуществить изменение действующих нормативно-правовых документов, регламентирующих проектирование систем пожарной сигнализации.</p>
   </abstract>
   <trans-abstract xml:lang="en">
    <p>To ensure the safety of citizens and protected facilities, fire alarm systems are designed and installed in high-rise buildings. One of the key design factors is the nature of smoke propagation during a fire, which in turn is highly dependent on ceiling height.&#13;
This study examines smoke propagation during a fire in high-rise buildings.&#13;
The study's methodology includes numerical modeling of this process, which was performed using Fire Dynamic Simulation software, followed by data visualization in Smokeview.&#13;
The data obtained indicate that at ceiling heights of 4 and 8 meters, vertical smoke accumulation occurs faster than horizontal smoke accumulation. Therefore, at these heights, traditional horizontal installation of linear smoke detectors is preferable. Above ceiling heights of 12 meters, vertical placement of linear smoke detectors is more advantageous. The identified characteristics can be useful both during the design and installation stages of fire alarm systems. As part of further research directions, it is advisable to study the process of smoke propagation with a smaller step in ceiling height and, based on the data obtained, make changes to the current regulatory documents governing the design of fire alarm systems.</p>
   </trans-abstract>
   <kwd-group xml:lang="ru">
    <kwd>распространение дыма</kwd>
    <kwd>высота помещения</kwd>
    <kwd>дымовой линейный извещатель</kwd>
    <kwd>опасные факторы пожара</kwd>
    <kwd>пожарная сигнализация</kwd>
    <kwd>FDS</kwd>
    <kwd>Smokeview</kwd>
   </kwd-group>
   <kwd-group xml:lang="en">
    <kwd>smoke spread</kwd>
    <kwd>room height</kwd>
    <kwd>linear smoke detector</kwd>
    <kwd>fire hazards</kwd>
    <kwd>fire alarm</kwd>
    <kwd>FDS</kwd>
    <kwd>Smokeview</kwd>
   </kwd-group>
  </article-meta>
 </front>
 <body>
  <p></p>
 </body>
 <back>
  <ref-list>
   <ref id="B1">
    <label>1.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Hu Yu., Wang X., Wang F.Yu. A quantitative study of factors influence on evacuation in building fire emergencies // IEEE transactions on computational social systems. 2018. Vol. 5. № 2. P. 544–552.</mixed-citation>
     <mixed-citation xml:lang="en">Hu Yu., Wang X., Wang F.Yu. A quantitative study of factors influence on evacuation in building fire emergencies // IEEE transactions on computational social systems. 2018. Vol. 5. № 2. P. 544–552.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B2">
    <label>2.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Зарипова Г.Ф., Маринич Е.Е. Разработка технических решений по ограничению распространения пожара в высотных зданиях // Студенческий. 2023. № 9-1 (221). С. 17–20. EDN YCJIVA.</mixed-citation>
     <mixed-citation xml:lang="en">Zaripova G.F., Marinich E.E. Razrabotka tekhnicheskih reshenij po ogranicheniyu rasprostraneniya pozhara v vysotnyh zdaniyah // Studencheskij. 2023. № 9-1 (221). P. 17–20. EDN YCJIVA.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B3">
    <label>3.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Моделирование дымовой завесы в охраняемом помещении / А.М. Пурис [и др.] // Вопросы оборонной техники. Сер. 16: Технические средства противодействия терроризму. 2021. № 1-2 (151-152). С. 91–97. EDN DKPFJG.</mixed-citation>
     <mixed-citation xml:lang="en">Modelirovanie dymovoj zavesy v ohranyaemom pomeshchenii / A.M. Puris [i dr.] // Voprosy oboronnoj tekhniki. Ser. 16: Tekhnicheskie sredstva protivodejstviya terrorizmu. 2021. № 1-2 (151-152). P. 91–97. EDN DKPFJG.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B4">
    <label>4.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Мясников В.Г., Степанов В.А. Специфика тушения пожаров в зданиях повышенной этажности // Студенческий. 2024. № 39-1 (293). С. 56–60. EDN YZGWGH.</mixed-citation>
     <mixed-citation xml:lang="en">Myasnikov V.G., Stepanov V.A. Specifika tusheniya pozharov v zdaniyah povyshennoj etazhnosti // Studencheskij. 2024. № 39-1 (293). P. 56–60. EDN YZGWGH.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B5">
    <label>5.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Rahmani A., Salem M. Simulation of fire in super high-rise hospitals using fire dynamics simulator (FDS) // Electronic Journal of General Medicine. 2020. Vol. 17. № 3. P. 5.</mixed-citation>
     <mixed-citation xml:lang="en">Rahmani A., Salem M. Simulation of fire in super high-rise hospitals using fire dynamics simulator (FDS) // Electronic Journal of General Medicine. 2020. Vol. 17. № 3. P. 5.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B6">
    <label>6.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Smith P. G. Fire-detection and alarm systems // Wiring Installations and Supplies. 1977. Vol. 1977. № 3. P. 9–19.</mixed-citation>
     <mixed-citation xml:lang="en">Smith P. G. Fire-detection and alarm systems // Wiring Installations and Supplies. 1977. Vol. 1977. № 3. P. 9–19.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B7">
    <label>7.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Inc U.L. Smoke Alarms // Underwriters Laboratories Inc. 2015.</mixed-citation>
     <mixed-citation xml:lang="en">Inc U.L. Smoke Alarms // Underwriters Laboratories Inc. 2015.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B8">
    <label>8.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Inc U.L. Smoke Detectors for Fire Alarm Systems // Underwriters Laboratories Inc. 2016.</mixed-citation>
     <mixed-citation xml:lang="en">Inc U.L. Smoke Detectors for Fire Alarm Systems // Underwriters Laboratories Inc. 2016.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B9">
    <label>9.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">National Fire Protection Association et al. Standard for automotive fire apparatus. The Association, 1996.</mixed-citation>
     <mixed-citation xml:lang="en">National Fire Protection Association et al. Standard for automotive fire apparatus. The Association, 1996.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B10">
    <label>10.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">National Fire Protection Association et al. NFPA 1901: Standard for automotive fire apparatus. The Association, 1996.</mixed-citation>
     <mixed-citation xml:lang="en">National Fire Protection Association et al. NFPA 1901: Standard for automotive fire apparatus. The Association, 1996.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B11">
    <label>11.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">NFPA N. 72: National Fire Alarm Signaling Code // National Fire Protection Association. 2013.</mixed-citation>
     <mixed-citation xml:lang="en">NFPA N. 72: National Fire Alarm Signaling Code // National Fire Protection Association. 2013.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B12">
    <label>12.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">NFPA P. J. NFPA 72 National Fire Alarm and Signaling Code. 2022.</mixed-citation>
     <mixed-citation xml:lang="en">NFPA P. J. NFPA 72 National Fire Alarm and Signaling Code. 2022.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B13">
    <label>13.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Experimental study on the characteristics of fire smoke movement in ultra thin and tall atriums by hot smoke test / H. Zhang [et al.] // E3S Web of Conferences. EDP Sciences, 2019. Vol. 79. P. 01007.</mixed-citation>
     <mixed-citation xml:lang="en">Experimental study on the characteristics of fire smoke movement in ultra thin and tall atriums by hot smoke test / H. Zhang [et al.] // E3S Web of Conferences. EDP Sciences, 2019. Vol. 79. P. 01007.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B14">
    <label>14.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">A Sauter mean diameter sensor for fire smoke detection / S. Wang [et al.] // Sensors and Actuators B: Chemical. 2019. Vol. 281. P. 920–932.</mixed-citation>
     <mixed-citation xml:lang="en">A Sauter mean diameter sensor for fire smoke detection / S. Wang [et al.] // Sensors and Actuators B: Chemical. 2019. Vol. 281. P. 920–932.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B15">
    <label>15.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Tilley N., Merci B. Numerical study of smoke extraction for adhered spill plumes in atria: Impact of extraction rate and geometrical parameters // Fire safety journal. 2013. Vol. 55. P. 106–115.</mixed-citation>
     <mixed-citation xml:lang="en">Tilley N., Merci B. Numerical study of smoke extraction for adhered spill plumes in atria: Impact of extraction rate and geometrical parameters // Fire safety journal. 2013. Vol. 55. P. 106–115.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B16">
    <label>16.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Huang Yu., Chen X., Zhang C. Numerical simulation of the variation of obscuration ratio at the fire early phase with various soot yield rate // Case Studies in Thermal Engineering. 2020. Vol. 18. P. 100572.</mixed-citation>
     <mixed-citation xml:lang="en">Huang Yu., Chen X., Zhang C. Numerical simulation of the variation of obscuration ratio at the fire early phase with various soot yield rate // Case Studies in Thermal Engineering. 2020. Vol. 18. P. 100572.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B17">
    <label>17.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">A Sauter mean diameter sensor for fire smoke detection / S. Wang [et al.] // Sensors and Actuators B: Chemical. 2019. Vol. 281. P. 920–932.</mixed-citation>
     <mixed-citation xml:lang="en">A Sauter mean diameter sensor for fire smoke detection / S. Wang [et al.] // Sensors and Actuators B: Chemical. 2019. Vol. 281. P. 920–932.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B18">
    <label>18.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">SFPE handbook of fire protection engineering / P.J. DiNenno [et al.] // (No Title). 2002. P. 2–246.</mixed-citation>
     <mixed-citation xml:lang="en">SFPE handbook of fire protection engineering / P.J. DiNenno [et al.] // (No Title). 2002. P. 2–246.</mixed-citation>
    </citation-alternatives>
   </ref>
   <ref id="B19">
    <label>19.</label>
    <citation-alternatives>
     <mixed-citation xml:lang="ru">Mulholland G.W., Croarkin C. Specific extinction coefficient of flame generated smoke // Fire and Materials. 2000. Vol. 24. № 5. P. 227–230.</mixed-citation>
     <mixed-citation xml:lang="en">Mulholland G.W., Croarkin C. Specific extinction coefficient of flame generated smoke // Fire and Materials. 2000. Vol. 24. № 5. P. 227–230.</mixed-citation>
    </citation-alternatives>
   </ref>
  </ref-list>
 </back>
</article>